Box fill
Check an outlet, device or junction box against NEC 314.16: the Table 314.16(A) or marked volume, every conductor, clamp, fitting, device yoke, grounding conductor and terminal block allowance, each line cited — NEC 2020 or 2023.
Check a box
How it works
The box's volume — from Table 314.16(A) for a standard metal box, or the volume marked on it — plus any marked plaster ring, extension ring or domed cover, against the sum of the allowances in 314.16(B): each counted conductor at its Table 314.16(B)(1) volume; one allowance for internal clamps; one per type of support fitting; two per device yoke; one for up to four grounding conductors and a quarter for each more; and, under NEC 2023, one per terminal block.
What it will not tell you
Conductors 4 AWG and larger — those boxes are sized by 314.28, not 314.16.
A box divided by a barrier — calculate each space on its own, with that space's volume.
Conduit bodies (314.16(C)).
The conductor count is yours: once for each conductor terminating or spliced, once passing through, twice for a long loop, zero for a pigtail. The page says the rule; it does not count a box it cannot see.
NEC 2020's listed clamp assemblies with cable terminations — their volume comes off the box, and that is the manufacturer's number.
No report, PDF or saved project — the answer is the whole of it.